IN-0042Monthly Building InspectionLow riskGoodClosed05 Aug 2026
Finding
Common areas in good order. Minor paint peeling on level 3 passage ceiling.
Recommendation
Include level 3 ceiling in next painting cycle.
Building: Bryanston CourtInspector: Pieter van WykArea: Common AreasPriority: Low 6 photographs
IN-0043Asset InspectionLow riskGoodClosed05 Aug 2026
Finding
Booster set running smoothly. Minor weep on pump 1 gland — within tolerance.
Recommendation
Monitor gland weep at next service.
Building: Bryanston CourtInspector: Pieter van WykArea: Basement Plant RoomAsset: Booster Pump Set 1Priority: Low 3 photographsFollow-up: 14 Dec 2026
IN-0044Water System InspectionHigh riskPoorIn Progress28 Jul 2026
Finding
Pump 2 mechanical seal leaking approx. 2L/hour. Abnormal noise from pump 3 bearings.
Recommendation
Replace mechanical seal on pump 2 immediately; budget for full set replacement within 12 months.
Building: Waterfall RidgeInspector: Pieter van WykArea: Basement B2 Pump RoomAsset: Main Booster Pump SetPriority: High 8 photographsFollow-up: 15 Aug 2026
Emergency repair — fire pump must auto-start. Verify hydrant pressure after repair.
Building: Sunninghill GardensInspector: Pieter van WykArea: Pump House, North GateAsset: Fire Booster PumpPriority: Critical 5 photographsFollow-up: 01 Aug 2026